This voltage drop calculator estimates how much voltage is lost along a copper wire run. Choose the wire size and enter the one-way length, current and supply voltage.

Voltage drop formula

Single-phase: VD = 2 × L × I × R ÷ 1,000
Three-phase: VD = √3 × L × I × R ÷ 1,000

L is the one-way length in feet, I the current in amps and R the wire resistance in ohms per 1,000 ft. The factor 2 counts the trip out and back.

Copper wire resistance (ohms per 1,000 ft, uncoated, 75°C)

SizeOhms / 1,000 ft
14 AWG3.07
12 AWG1.93
10 AWG1.21
8 AWG0.764
6 AWG0.491
4 AWG0.308
3 AWG0.245
2 AWG0.194
1 AWG0.154
1/0 AWG0.122
2/0 AWG0.0967
3/0 AWG0.0766
4/0 AWG0.0608

Example

A 15 A load 100 ft away on 12 AWG copper at 120 V drops 2 × 100 × 15 × 1.93 ÷ 1,000 = 5.79 V (4.8%), leaving 114.2 V at the load. Going up to 10 AWG would cut that to about 3.6 V (3%).

Tips

  • The US National Electrical Code includes an informational note suggesting no more than 3% drop on a branch circuit and 5% overall.
  • Wire size must also meet the ampacity rules for the circuit, which this calculator doesn't check; a licensed electrician should confirm.
  • Find the current from wattage with the watts to amps calculator.

Frequently asked questions

What is an acceptable voltage drop?

A common guideline is 3% or less on branch circuits and 5% total from service to load.

Does longer wire mean more voltage drop?

Yes, drop increases in proportion to length.

Why use the one-way length?

The formula already doubles it to include the return path.