Voltage drop formula
Single-phase: VD = 2 × L × I × R ÷ 1,000
Three-phase: VD = √3 × L × I × R ÷ 1,000
L is the one-way length in feet, I the current in amps and R the wire resistance in ohms per 1,000 ft. The factor 2 counts the trip out and back.
Copper wire resistance (ohms per 1,000 ft, uncoated, 75°C)
| Size | Ohms / 1,000 ft |
|---|---|
| 14 AWG | 3.07 |
| 12 AWG | 1.93 |
| 10 AWG | 1.21 |
| 8 AWG | 0.764 |
| 6 AWG | 0.491 |
| 4 AWG | 0.308 |
| 3 AWG | 0.245 |
| 2 AWG | 0.194 |
| 1 AWG | 0.154 |
| 1/0 AWG | 0.122 |
| 2/0 AWG | 0.0967 |
| 3/0 AWG | 0.0766 |
| 4/0 AWG | 0.0608 |
Example
A 15 A load 100 ft away on 12 AWG copper at 120 V drops 2 × 100 × 15 × 1.93 ÷ 1,000 = 5.79 V (4.8%), leaving 114.2 V at the load. Going up to 10 AWG would cut that to about 3.6 V (3%).
Tips
- The US National Electrical Code includes an informational note suggesting no more than 3% drop on a branch circuit and 5% overall.
- Wire size must also meet the ampacity rules for the circuit, which this calculator doesn't check; a licensed electrician should confirm.
- Find the current from wattage with the watts to amps calculator.
Frequently asked questions
What is an acceptable voltage drop?
A common guideline is 3% or less on branch circuits and 5% total from service to load.
Does longer wire mean more voltage drop?
Yes, drop increases in proportion to length.
Why use the one-way length?
The formula already doubles it to include the return path.